Solution: Make good insulation layer, eliminate water vapor, and no cold bridge between the indoor wall and the outdoor
1, the reason for condensation is that the temperature of the plate is lower than the dew point (the temperature when condensation occurs), and there is water vapor in the room.
The solution is to increase the insulation effect, so that the difference between the surface temperature and room temperature is generally within 3 degrees.
2, the glass wool absorbs a lot of water, and the insulation effect is greatly reduced after absorbing water.
It is recommended to make a vapor insulation layer (that is, aluminum foil or white polypropylene veneer, requiring the paste to face the room) to prevent water vapor from entering the insulation layer. And improve the insulation thickness, generally increased to 1.7 times.
3, increase ventilation: ventilation will reduce the room temperature, reduce the temperature difference on the board surface, and reduce the indoor relative humidity.
4. Suspended ceiling to form attic.
The air separation itself is insulation, and at the same time, the attic can be ventilated separately.
5, light steel structure metal roof roof special power-free turbine ventilation ventilator and roof ridge ventilation ventilator, one-time cost investment is high, production and use of energy consumption and maintenance costs are almost zero, reasonable design layout can ensure good results within the scope of the plant, but the loss of indoor heat.
6, the metal roof is a single-layer pressed plate under the steel wire mesh, the middle of the aluminum foil glass wool (hereinafter referred to as single), or the double-layer steel plate in the middle of the glass wool (hereinafter referred to as double) two practices.
Pay attention to both methods:
(1), the use of single-sided aluminum foil glass wool, in the entire roof installation must pay attention to ensure that it is continuous without missing or disconnecting to eliminate cold bridge, aluminum foil tape connection to ensure steam tightness.
(2), the metal roof single method of laying wire mesh pay attention to the tension of the wire mesh to ensure that it is properly overhung between adjacent purlins, in case of emergency, the inverted nail board is laid above the production line to prevent condensation from dripping into the production line; It must be noted that the indoor roof panels should be laid in the order from the ridge to the eaves, and the eaves gutter design should consider the corresponding condensate extraction structure. The prevention of condensation is very important for light steel structure workshops with large evaporation in production. Possible: glass wool due to absorption of condensate resulting in a doubling of the roof load, condensate dripping into the production line resulting in equipment and product fouling, indoor environment deterioration and so on.